Home View Cart Contact Us Sitemap Order Status

Access Control
Alarm Monitoring
Alarm System FAQ
Anti-Theft Devices
Audio Monitoring - Louroe
Biometrics
Burglar Alarm System Packages
Burglar Alarm Systems
CCTV Video Surveillance
Central Station Equipment
Central Vacuum
Document Center
Driveway Alarms
Entertainment Systems
Extreme CCTV
Fiber Optics
Fire Alarm Systems
Gas Detectors & Alarms
GE Security
Home Automation
Intercom Systems
Locksmith Supplies
Marine Alarms
On-Q Home
Other Stuff
Power Supplies
Professional Audio
Sensors and Detectors
Sirens, Strobes & Horns
Structured Wiring
Telephone Systems
Tools & Test Equipment
Warrantees
Wire & Cable
Z-Wave Home Automation
Discontinued Products
Shop by Brand

Fire Alarm Systems > FireLite Alarms > Addressable Detectors and Modules
Addressable Detectors and Modules

FireLite Addressable Detectors & Modules

BEAM355 Intelligent, Addressable Projected Beam Smoke Detector

FireLite BEAM355 Addressable Projected Beam Smoke Detector

The Fire·Lite BEAM355 and BEAM355S are intelligent, addressable projected beam smoke detectors for protecting open areas with high and sloping ceilings, and wideopen areas, where spot-type smoke detectors are difficult to install and maintain. Ideal applications are atriums, cathedral ceilings, aircraft hangers, warehouses, sporting arenas, concert halls, and enclosed parking facilities. They are compatible with the MS-9600 and MS9200UD addressable Fire Alarm Control Panels (FACPs). Installation of the single-ended reflective design is much quicker than a dual-ended projected beam detector. Alignment is easily accomplished with an optical sight and a two-digit signal strength meter incorporated into the beam detector. Listed for operation from –22ºF to 131ºF, the BEAM355 and BEAM355S are usable in open area applications where temperature extremes exceed the design limits of other types of smoke detection.

The BEAM355 and BEAM355S are a transmitter/receiver unit and a reflector. When smoke enters the area between the unit and the reflector, it causes a reduction in the signal strength. When the smoke level (signal strength) reaches the predetermined threshold, an alarm is activated. The detectors have four standard sensitivity selections as well as two Adapt™ settings. When either Adapt™ setting is selected, the detector's advanced software algorithms automatically adjust to the optimum sensitivity for the specific environment. The protection range is 16 to 328 feet and there are built-in isolators for Style 7 operation.

The BEAM355S has an integral sensitivity test feature of a filter attached to a servomotor inside the detector optics. Activation of the RTS451 remote test station moves the filter into the pathway of the light beam, testing the detector's sensitivity. This sensitivity test feature allows the user to quickly and easily meet the annual maintenance and test requirements of NFPA 72, without physical access to the detector.

Features

  • Transmitter/receiver built into same unit.
  • Six user-selectable sensitivity levels.
  • 16' to 328' (use BEAMLRK beyond 230') protection range.
  • Removable plug-in terminal blocks.
  • Digital display – no special tools required.
  • Built-in automatic gain control compensates for signal deterioration from dust buildup.
  • Optional remote test station.
  • Optional long-range kit (BEAMLRK) for applications in excess of 230' (70 m).
  • Optional multi-mount kit (BEAMMMK) providing ceiling or wall mount capability with increased angular adjustment.
  • Optional heater kits (BEAMHK and BEAMHKR) for prevention of condensation (not intended to increase or reduce the specified operating temperature).

Operational Specifications

Protection range: 16 to 230 feet (5 to 70 m), 230 to 328 feet (70 to 100 m) using optional BEAMLRK kit.

Adjustment angle: ±10º horizontal and vertical. Note that the optics move independently of the unit.

Sensitivity (6 levels):
  • Level 1 – 25%.
  • Level 2 – 30%.
  • Level 3 – 40%.
  • Level 4 – 50%.
  • Adapt™ Level 5 – 30% to 50%.
  • Adapt™ Level 6 – 40% to 50%.
Fault condition (trouble):
  • 96% or more obscuration blockage.
  • In alignment mode.
  • Improper initial alignment.
  • Self-compensation limit reached.
Alignment aid:
  • Optical gunsight.
  • Integral signal strength indication.
  • Two-digit display.
Indicators:
  • Alarm – local red LED and remote alarm.
  • Trouble – local yellow LED and remote trouble.
  • Normal – local flashing green LED.
Test/reset features:
  • Integral sensitivity test filter (BEAM355S only, requires external power supply).
  • Sensitivity filter (incremental scale on reflector).
  • Local alarm test switch.
  • Local alarm reset switch.
  • Remote test and reset switch (compatible with RTS451 and RTS451KEY test stations).

Smoke detector spacing: On smooth ceilings, 30 – 60 feet (9.1 to 18.3 m) between projected beams and not more than one-half that spacing between a projected beam and a sidewall. Other spacing may be used depending on ceiling height, airflow characteristics, and response requirements. See NFPA 72.

Environmental Specifications
  • Temperature: –22ºF to 131ºF (–30ºC to 55ºC).
  • Humidity: 10 – 93% RH noncondensing.
Electrical Specifications
  • Voltage: 15 to 32 VDC.
  • Average standby current (24 VDC): 2 mA maximum (LED flashing, SLC @ 24 V).
  • LED current: 6.5 mA maximum.
  • Remote annunciator current: 11.2 mA maximum.
  • Average current during testing: 500 mA maximum.
  • Alarm current (24 VDC): 8.5 mA maximum (LED on).
  • Trouble/fault current (24 VDC): 4.5 mA maximum (LED on).
  • Fault condition current (add to standby current): 100 mA maximum.
  • Alignment mode current (24 VDC): 20 mA maximum.
  • External supply (FSB-200S only): Voltage: 15 to 32 VDC.
  • Current: 0.5 A maximum.
  • Remote output (alarm): Voltage: 15 to 32 VDC. NOTE: Output voltage is the same as device input voltage.
  • Current: 15 mA maximum, 6 mA minimum. NOTE: Output current is limited by 2.2K ohm resistor.
  • Heater kit BEAMHK: Voltage: 15 to 32 V. Current: 92 mA maximum @ 32 V (heater only).
  • Power consumption: nominal 1.6 W @ 24 V; maximum 3.0 W @ 32 V.
  • Heater kit BEAMHKR: Voltage: 15 to 32 V.
  • Current: 450 mA maximum @ 32 V (per reflector).
  • Power consumption (per reflector): nominal 7.7 W @ 24 V; maximum 15.0 W @ 32 V.
Mechanical Specifications
  • Detector dimensions: 10.0" H x 7.5" W x 3.3" D (254 mm H x 191 mm W x 84 mm D).
  • Reflector dimensions for 16' to 230' (5 to 70 m) applications: 7.9" x 9.1" (200 x 230 mm).
  • Reflector dimensions for applications beyond 230'/70 m: 15.7" x 18.1" (400 x 460 mm).


 
BEAM355 Intelligent, Addressable Projected Beam Smoke Detector

Note: Images include optional items which may be ordered separately.

[Printable View]