FireLite MRP-2001 Deluge/Preaction Control Panel
The MRP-2001 is a six-zone FACP for single and dual hazard deluge and preaction applications. The MRP-2001 provides reliable fire detection, signaling and protection for commercial, industrial and institutional buildings requiring water-based releasing. The MRP-2001 is compatible with System Sensor's i3 detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory 'freeze' signal when the ambient temperature falls below the detector rating of approximately 45ºF (7.22ºC). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Fire·Lite Device Compatibility Document for a complete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing circuits. Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory) and 24 VDC special application resettable and non-resettable power outputs are also included on the main circuit board. The MRP-2001 supervises all wiring, AC voltage, battery charger and battery level.
Activation of a compatible smoke detector or any normallyopen fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm information on the panel's LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate an auxiliary control function.
The MRP-2001E offers the same features as the MRP-2001 but allows connection to 220/240 VAC. Unless otherwise specified, the information in this data sheet applies to both the 110/120 VAC and 220/240 VAC versions of the panels.
Features
- Listed to UL Standard 864, 9th edition.
- Designed for sprinkler standards NFPA 13, 15 and 16.
- Dual hazard operation.
- Adjustable waterflow discharge timer and two soak timers.
- Cross-zone (double-interlock) capability.
- Six programmable Style B (Class B) IDCs (Initiating Device Circuit).
- System Sensor i3 series detectors compatible.
- Four programmable Style Y (Class B) output circuits - (special application power).
- Strobe Synchronization:
– System Sensor
– Wheelock
– Gentex
– Faraday
– Amseco
- Three programmable Form-C relays.
- 7.0 amps total 24 VDC output current.
- Resettable and non-resettable output power.
- Built-in Programmer.
- ANN-BUS for connection to optional (up to 8 total of any of the following):
– ANN-80 Remote LCD Annunciator
– ANN-I/O LED Driver
– ANN-S/PG Printer Module
– ANN-RLY Relay Module
– ANN-LED Annunciator Module
- 80-character LCD display (backlit).
- Real-time clock/calendar with daylight savings time control.
- History log with 256 event storage.
- Piezo sounder for alarm, trouble and supervisory.
- 24 volt DC operation.
- Low AC voltage sense.
- Outputs Programmable for:
– Releasing circuits or NACS
- NACs programmable for:
– Silence Inhibit
– Auto-Silence
– Strobe Synchronization
– Selective Silence (horn-strobe mute)
– Temporal or Steady Signal
– Silenceable or Non-silenceable
– Release Stage Sounder
- Disable/Enable control per input zone and output zone.
- Extensive transient protection.
- Automatic battery charger with charger supervision.
- Optional Dress Panel DP-51050 (red).
- Optional Trim Ring TR-CE (red) for semi-flush mounting the cabinet.
- Optional CAC-5X Class A Converter Module for Outputs and IDCs.
- Optional 4XTMF Municipal Box Transmitter Module.
- Optional Digital Alarm Communicators (411, 411UD, 411UDAC).
|
|
|
| |
 |