Honeywell FF8 Notification Appliance Circuit (NAC) Power Supply
The FireForce 8 (FF8) is a Notification Appliance Circuit (NAC) extender panel designed to extend the power capabilities of existing NACs and provide power for other ancillary devices. The FF8 will connect to any brand of UL-Listed Fire Alarm Control Panel (FACP) to provide Notification Appliance Circuit expansion. Designed with advanced switch-mode power-supply technology, the FireForce 8 provides filtered and electronically regulated power distributed to four NACs. Each NAC is rated at 3.0 Amp maximum, aux power rated 1.5 Amp, with a total output capacity of 8.0 Amp. The outputs may be configured as: four Class B (Style W, X, Y); or two Class A (Style Z); or two Class B and one Class A; or four Class A (Style Z) with the optional Class A adaptor installed. The FF8 includes an internal battery charger.
Specifications
- Primary input power: 120 VAC, 60 Hz, 3.0 A; or 220 V
- 1.5 A; jumper selectable.
- Secondary power: 24-volt operation, two 7 - 24 AH batteries.
- Battery charging capacity: up to 26 AH batteries.
- Battery space: up to two 12 AH batteries maximum inside FF8 cabinet. Larger batteries require a separate battery cabinet.
- Standby current: 0.040 A.
- Auxiliary power output: 0.15 A under all conditions. 1.5 A, if load is removed during operation (external relay or AC Fail relay use required.
- NAC output ratings: 24 VDC fully regulated, 3.0 A maximum per circuit (8.0 A total).
- End-of-Line resistor range: 2K to 25K, 1/2 watt.
- Common trouble relay, AC Fail relay: 2.0 A/28 VDC or 120 VAC.
- Input control circuit: 16 - 30 VDC @ 5 mA minimum.
- Temperature rating: 32ºF to 120ºF (0ºC to 49ºC).
- Relative humidity: 10 - 93%, non-condensing.
- Dimensions: FF8 cabinet: 18.0" H x 12.5" W x 4.5" D (cm: 45.72 H x 31.75 W x 11.43 D).
- UL Listed: file S6677.
- MEA: 206-01-E Vol II
- CSFM: 7300-1637:100
- FM Approved
|
|
|
| |
 |
|
|