MS-9600 Rev. 2/DACT-UD Intelligent Addressable FACP with Optional 2nd Loop
The Fire•Lite MS-9600 is a compact, cost-effective, intelligent addressable fire alarm control panel with a capacity
of 318 addressable Fire•Lite devices on one Signaling Line Circuit (SLC) or a total of 636 addressable points with an
optional second loop (SLC-2). An optional 14.4K Baud modem (DACT-UD) is available for remote site upload/download and/or
remote monitoring.
Each Signaling Line Circuit (SLC) loop supports up to 159 addressable detectors including photoelectric, photoelectric
with heat, ionization, photoelectric duct, fixed heat, fixed heat with rate-of-rise, and fixed high-heat detectors. It also
supports up to 159 addressable modules including monitor (twowire detector, normally open devices), dual-monitor functions
(two monitor circuits from one module, two addresses used), control (for Notification Appliance Circuits), and relay (two
Form-C) modules. The panel uses surface-mount technology and is designed for ease of installation, programming, and
maintenance. It features the latest in advanced fire protection technology, including maintenance alert and automatic
detector test functions.
Special Features:
- Optional 14.4K Baud modem.
- Selectable strobe synchronization per NAC.
- Remote site upload/download.
- Four Class B or two Class A NAC circuits.
SLC Loop:
- SLC can be configured for NFPA Style 4, 6, or 7 operation.
- SLC supports up to 318 addressable devices per loop (159 detectors and 159 monitor, control, or relay modules), including the new addressable dual-monitor module, heat detectors, and duct detector.
- SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG (3.25 mm˛). Requires twisted, shielded wire (3,000 ft./914.4 m untwisted, unshielded wire).
Notification Appliance Circuits (NACs):
- Four onboard NACs with additional NAC capability using output control modules (CMF-300 or CMF-300-6).
- Silence Inhibit and Auto Silence timer options.
- Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability.
- Selectable strobe synchronization per NAC.
- 7.0 amps total NAC power.
Advanced Fire Technology:
- Sensitivity testing with printable results, onsite or offsite.
- Automatic drift compensation.
Programming and Software:
- Autoprogram (learn mode) reduces installation time.
- Fully programmable from local keypad, local PS-2 keyboard or PC via PK-Plus Windows® utility.
- Remote site upload/download capability (with DACT-UD).
- Two-level user-programmable passwords.
- Custom English labels (per point) may be manually entered or selected from an internal library file.
- Two programmable Form-C relay outputs.
- 99 software zones.
User Interface:
- Optional 14.4K Baud modem (DACT-UD).
- Remote Acknowledge, Silence, Reset and Drill via addressable monitor modules, ACS Series annunciators or LCD-80F remote annunciator.
- EIA-232 printer/PC interface (variable baud rate) on main circuit board.
- Integral 80-character LCD display with backlighting.
- Real-time clock/calendar with automatic daylight savings adjustments.
- History file with 1,000-event capacity.
- EIA-485 supporting up to 32 ACS Series annunciators.
- EIA-485 supporting up to 32 LCD-80F annunciators.
- Maintenance alert warns when smoke detector dust accumulation is excessive.
- Automatic device type-code verification.
- One person audible or silent walk test with walk-test log and printout.
- Point trouble identification.
- Local piezo sounder.
- Waterflow (nonsilenceable) selection per monitor point.
- System alarm verification selection per detector point.
- PAS (Positive Alarm Sequence) and presignal delay per point (NFPA 72 compliant).
- Optional 4XTMF module (conventional reverse polarity/city box transmitter).