FireLite MS-99200UDLS 198-Point Intelligent Fire Alarm Control Panel
Fire-Lite's MS-9200UDLS Intelligent Addressable Fire Alarm System with new LiteSpeedTM SLC protocol is ideal for small to medium facilities.
The cost efficient MS-9200UDLS consists of a single PC board, including all electronics, a 3 amp power supply, built-in digital communicator and
support for 198 addressable devices on one signaling line circuit (SLC).
It is designed for ease of installation, programming and operability to meet
any application requirement and to grow as your customers' needs expand.
The MS-9200UDLS comes standard with a user-friendly LCD Display, 4 NAC circuits with built-in synchronization for System Sensor, Wheelock
and Gentex devices, two programmable relays and support for up to 32 optional LCD-80F or ACS LED annunciators. The 3-amp power supply can
be expanded to 6 amps with a low-cost transformer assembly providing up to 5 amps for external devices.
Features
- On-board DACT.
- Four Class B or two Class A NAC circuits.
– 6.0 amps total NAC power with optional XRM-24.
- Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices.
- Complies with UL 864 9th Edition requirements.
- Remote Acknowledge, Silence, Reset and Drill via addressable monitor modules.
- Up to 32 ACM Series (ACM-16AT or ACM-32 series) annunciators or LCD-80F remote annunciators via EIA-485.
- EIA-232 printer/PC interface (variable baud rate) on main circuit board.
- Integral 80-character LCD display with backlighting.
- Real-time clock/calendar with automatic daylight savings control.
- Detector sensitivity test capability (NFPA 72 compliant).
- History file with 1,000-event capacity.
- Maintenance alert warns when smoke detector dust accumulation is excessive.
- Automatic device type-code verification.
- One person audible or silent walk test with walk-test log and printout.
- Point trouble identification.
- Waterflow (nonsilenceable) selection per monitor point.
- System alarm verification selection per detector point.
- PAS (Positive Alarm Sequence) and presignal delay per point (NFPA 72 compliant).
SLC Communications Loop
- SLC can be configured for NFPA Style 4, 6, or 7 operation.
- SLC supports up to 198 addressable devices per loop (99 detectors and 99 monitor, control, or relay modules).
- SLC loop maximum length 10,000 ft. (3,000 m).
Notification Appliance Circuits (NAC's)
- Four onboard NACs with additional NAC capability using output control modules (CMF-300 or CMF-300-6).
- Silence Inhibit and Auto Silence timer options.
- Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability.
- Selectable strobe synchronization per NAC.
- 2.5 amps maximum per each NAC circuit.
Programming and Software
- Autoprogram (learn mode) reduces installation time.
- Custom English labels (per point) may be manually entered or selected from an internal library file.
- Two programmable Form-C relay outputs.
- 99 software zones.
- Continuous fire protection during online programming at the front panel.
- Program Check automatically catches common errors not linked to any zone or input point.
|
|
|
| |
 |
|
|